摘要:
 考察了变压器油的温度对Teflon-AF/陶瓷复合膜组件油气分离性能的影响。当变压器油温由40 °C增加到60 °C时,Teflon-AF/陶瓷复合膜不仅能够缩短各故障气体的平衡时间,而且还能显著提高气体的平衡浓度,其中H2的平衡浓度提高约30%,CO提高约40%,烃类提高约10%。实验表明恰当的油温能够有效改善Teflon-AF/陶瓷复合膜脱气效果。根据这一规律设计制作了具有油温恒温控制功能的脱气装置,使变压器油温恒定在60 °C,可以在1.5 h内实现6种故障特征气体的油气平衡,而且监测数据更加准确可靠,有望在变压器在线监测产品中推广应用。
 The effect of oil temperature on the oil-gas separation characteristics of Teflon-AF/ceramic composite membrane module was studied. When the temperature increased from 40 °C to 60 °C, the Teflon-AF/ceramic composite membrane could not only shorten the equilibrium time of all the fault gases, but also remarkably enhance the equilibrium concentration of H2 by about 30%, CO by about 40%, and hydrocarbons by about 10%, indicating that the proper oil temperature can improve the degassing efficacy of this membrane. A temperature-controllable degassing machine has been designed based on the he experimental results and on which, the oil-gas equilibrium time reduced from 5h to 1.5h and the monitoring data obtained was more precise and repeatable. The machine is quite applicable to the dissolved gas-in-oil monitoring system.
第一作者简介:禚莉(1983-),女,江苏徐州人,硕士,工程师,江苏国电南自海吉科技有限公司,主要从事变压器在线监测系统研究。E-mail:zhuoli0412@163.com

参考文献:
 [1] Duval M. A review of faults detectable by gas-in-oil analysis in transformers[J]. IEEE Elec. Insul. Magaz. 2002, 18(3): 8–17.
[2] On-line Transformer incipient Fault Monitoring Device, HYDRAN201 series, their Properties, Configuration and Installation, Zhongneng Electric Power Developing Company, 1999. 1.
[3] 善学雷. 变压器油中溶解气体在线监测技术的进展[J]. 电气开关,2010, 48(6):1–4.
[4] 李洋流. 基于膜分离与光声光谱的绝缘油中溶解气体在线分析技术[D]. 哈尔滨工业大学,2011.
[5] 禚莉.变压器油气分离膜的制备及性能研究 [D].南京工业大学,2008.
[6] 禚莉,韩毓旺,俞斌. 陶瓷- Teflon A F2400复合油气分离膜组件[J]. 膜科技与技术, 2009, 29(5): 83–87.
[7] Han Yuwang, Ding Fei, Hao Chanxi,et al. The oil–gas separation characteristics of ceramic/Teflon AF2400 composite membrane[J]. Sep Purif Technol, 2012, 88(19): 19–23.
[8] 何鹏,赵学增,李洋流. 基于膜分离的变压器在线监测中温度对油气分离影响的研究[J]. 变压器,2011, 48(7): 45–49.
 